6. Daily Maintenance and Periodic Inspection and Maintenance 
6.1  Maintenance Tools 
 
 
 
III-37
 
6.  Daily Maintenance and Periodic Inspection and Maintenance 
 
6.1  Maintenance Tools 
 
(1) Measuring 
instruments 
The following measuring instruments are used to confirm that the voltage is being supplied correctly to the 
NC unit, to confirm that the wiring to the NC unit is correct, and to carry out simple troubleshooting. 
 
Tool Condition 
Application 
Tester 
 
To check that the wiring to the NC unit is correct 
before turning the power ON. 
AC voltmeter 
Measure the AC power voltage.  
The tolerable error is 
±2%  
or less. 
To measures the AC power voltage being 
supplied to the external 24VDC power supply 
unit. 
DC voltmeter  Max. scale 30V.  
The tolerable error is 
±2%  
or less. 
To measure the DC power voltage. 
External power supply 24V (control section, 
machine input/output interface) 
Battery voltage  
HR081/HR082/HR083 DC output 
Phase rotation 
meter 
 
To check the connection order of the AC 3-phase 
input power supply. 
Oscilloscope 
 
General measurement and simple 
troubleshooting 
(Note 1)  Currently, a high-accuracy digital multi-meter is commonly used as a tester. This digital 
multi-meter can be used as both an AC voltmeter and an DC voltmeter. 
(Note 2)  A logic analyzer (sampling cycle 200MHz or more) is required for complicated troubleshooting. 
 
(2) Tools 
   Screwdriver (large, medium, small) 
   Radio pliers 
 
6.2  Maintenance Items 
 
Maintenance is categorized into daily maintenance items (items to be carried at set intervals) and periodic 
maintenance items (replacement of parts when life is reached).  
Some parts will not function in a hardware manner when the life is reached, so these should be replaced 
before the life is reached. 
Class Name 
Life 
Inspection/replacement 
Remarks 
Daily 
maintenance 
Escutcheon  
Once/two 
months 
(Accordingly when dirty) 
 
Periodic 
maintenance 
Battery  
(lithium battery) 
Cumulative data 
holding time 
     45,000 hr 
When battery voltage 
drop caution alarm occurs 
(Guideline: approx. 5 
years) 
Refer to 
Section 
6.3.2 (1). 
 Cooling 
fan 
 
(control section) 
30,000 hr 
Refer to left. 
 
Other 
consumable 
parts 
Operation board 
10
6
 punches 
Refer to left.