APC AP7900 Manual Do Utilizador
®
USER’S GUIDE
Switched Rack PDU
8
Upgrading Firmware through a Serial Connection
You can use a local computer that connects to the Rack PDU through the
serial port on the front panel of the unit.
serial port on the front panel of the unit.
1. Select a serial port at the local computer, and disable any service
which uses that port.
2. Use the supplied serial cable (940-0144) to connect the selected port
to the serial port on the front panel of the Rack PDU.
3. Run a terminal program (such as HyperTerminal) and configure the
selected port for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow
control. Save the changes.
control. Save the changes.
4. Press
E
NTER
, repeatedly if necessary, to display the
User Name
prompt.
5. Enter your user name and password (both
apc
, by default, for
administrators only) and press the
E
NTER
key.
6. From the
Control Console
menu, select, in order,
System
,
Tools
,
File
Transfer
, and
XMODEM
.
7. At the prompt
Perform transfer with XMODEM-CRC?
type
YES
,
and press
E
NTER
.
8. The system will then prompt you to choose a transfer rate and to
change your terminal settings to match the transfer rate. Press
E
NTER
to set the Switched Rack PDU to accept the download.
For a complete description of how to download a firmware upgrade
for your Rack PDU, see
for your Rack PDU, see
.
That section also explains how to use network-based file transfer
tools, which complete a firmware upgrade more quickly than the
XMODEM protocol described here, which uses a serial connection.
tools, which complete a firmware upgrade more quickly than the
XMODEM protocol described here, which uses a serial connection.