Upgrading Firmware through a Serial Connection
You can use a local computer that connects to the Rack PDU through the 
serial port on the front panel of the unit.
1. Select a serial port at the local computer, and disable any service 
which uses that port.
2. Use the supplied serial cable (940-0144) to connect the selected port 
to the serial port on the front panel of the Rack PDU. 
3. Run a terminal program (such as HyperTerminal) and configure the 
selected port for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow 
control. Save the changes.
4. Press 
E
NTER
, repeatedly if necessary, to display the 
User Name
 
prompt.
5. Enter your user name and password (both 
apc
, by default, for 
administrators only) and press the 
E
NTER
 key.
6. From the 
Control Console
 menu, select, in order, 
System
Tools
File
 
Transfer
, and 
XMODEM
.
7. At the prompt 
Perform transfer with XMODEM-CRC?
 type 
YES
and press 
E
NTER
.
8. The system will then prompt you to choose a transfer rate and to 
change your terminal settings to match the transfer rate. Press 
E
NTER
 
to set the Switched Rack PDU to accept the download.
For a complete description of how to download a firmware upgrade 
for your Rack PDU, see 
That section also explains how to use network-based file transfer 
tools, which complete a firmware upgrade more quickly than the 
XMODEM protocol described here, which uses a serial connection.