APC AP7900 Manual Do Utilizador

Página de 186
®
USER’S GUIDE
Switched Rack PDU
6
How to Recover From a Lost Password
You can use a local computer, a computer that connects to the Rack PDU 
or other device through the serial port to access the control console.
1. Select a serial port at the local computer, and disable any service that 
uses that port.
2. Connect the serial cable (990-0144) to the selected port on the 
computer and to the configuration port at the Rack PDU:
3. Run a terminal program (such as HyperTerminal
®
) and configure the 
selected port as follows:
– 9600 bps
– 8 data bits
– no parity
– 1 stop bit
– no flow control
4. Press 
E
NTER
, repeatedly if necessary, to display the 
User Name
 
prompt. If you are unable to display the 
User Name
 prompt, verify the 
following:
– The serial port is not in use by another application.
– The terminal settings are correct as specified in step 3.
– The correct cable is being used as specified in step 2.
5. Press the 
Reset
 button. The Status LED will flash alternately orange 
and green. Press the 
Reset
 button a second time immediately while 
the LED is flashing to reset the user name and password to their 
defaults temporarily.
6. Press 
E
NTER
 as many times as necessary to redisplay the 
User Name
 
prompt, then use the default, 
apc,
 for the user name and password. (If 
you take longer than 30 seconds to log on after the 
User Name
 prompt 
is redisplayed, you must repeat step 5 and log on again.)