DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-8
AC-POWER 
10
AC-POWER 
AC Power for AC-Powered Systems
NOTE:
For environment maintenance, PPN or EPN cabinet configuration aspects 
in a high or critical reliabilty system are irrelevant.
The environment maintenance strategy to be used depends on both the cabinet 
configuration and the type of powering. Also refer to the DC-POWER (DC Power) 
for environment maintenance strategy.
The AC Power MO represents the AC power provided to the system from a wall 
outlet. The AC power comes from the wall outlet, through the Power Distribution 
Unit (PDU), if installed, and is then distributed to the various cabinets. The 
battery charger monitors AC power via fuse F3. See Figure 10-1. If no PDU is 
installed, the power is supplied directly to each cabinet from each individual wall 
outlets.
When the system loses power (for example, a power outage in the building), a 
Major alarm is logged against AC Power and the system goes on battery backup, 
which is known as Nominal Power Holdover (NPH). If power is restored before 
the NPH time expires, the alarm is resolved. Each basic control cabinet has 
separate batteries for NPH. The nominal power holdover provided is as follows:
The batteries power the system for 10 seconds in a PPN cabinet, for 15 
seconds in an EPN cabinet, and for 10 minutes in the control carrier in a 
standard reliability system.
The batteries also provide system power for five minutes in the control 
carrier in high and critical reliability systems.
!
WARNING:
Before powering down a cabinet or carrier that contains DEFINITY AUDIX 
circuit packs (TN566), first power down the AUDIX unit to avoid damaging 
the AUDIX software. Instructions for powering down this unit are in the 
"DEFINITY AUDIX System Power Procedures" in Chapter 5, "Routine 
1.
Where P is an appropriate port network number determined via the PORT field from 
the Alarm or Error Log.
MO Name (in 
Alarm Log)
Alarm Level
Initial Command to Run
1
Full Name of 
MO
AC-POWER
WARNING
test environment P
AC Power