Section 1
General Information
Parameter Index 4-13
MN850
Title
P#
Parameter
Description
Parameters
Continued
86
Auto Config 2 (for 2nd param set)
Auto configuration flags for the second
parameter set.
Definition (Preset Value)
Bit0=  Unused
Bit1= Auto 3MC (1, enable auto removal of low voltage ramp for 
high start pedestals)
Bit2= Auto Bypass (1, enable automatic bypass contactor detection).
Bit3= Auto Jog (0, disable jog detection. If enabled a stop request within 
0.5 second of a start request is forced to 0 stop time).
Bit4= Auto Endstop (0, disabled. If enabled detect a stalled motor during 
softstop and turn off thyristors).
Bit5= Auto Stop (0, do not detect variations in pf during stop smooth stall).
Bit6= Auto Endstart (0, disable detection of full speed during start and 
end of start ramp)
Bit7= Auto Pedestal (0, disable detection of motor rotation at start with 
pedestal adjustment).
Parameters
P87
Under Current 2 (for 2nd param set)
Sets the under current trip level.
Continued
P88
Under Current Time 2 (for 2nd param set)
The time allowed for a low current level condition (P87) to exist
before tripping.  For 60 Hz, 40 cycles = 667ms. 
For 50 Hz, 40 cycles = 800ms.
P89
Current Limit 2 (for 2nd param set)
Sets the motor starting current.
90
(for 2nd param set)
The time allowed for start current to equal P89 value before tripping.
Note that for 60 Hz, 40 cycles = 667ms. 
For 50 Hz, 40 cycles = 800ms.
91
Shearpin 2 (for 2nd param set)
Sets the over current trip level. Shearpin operation begins after
start–up is complete.
92
(for 2nd param set)
The number of cycles allowed for an overcurrent condition before
tripping (only when shearpin flag P95, Bit3=1).  For 60 Hz, 60 cycles
= 1second. For 50 Hz, 50 cycles = 1second.
93
(for 2nd param set)
Sets the overload current level as a portion of FLA.  (P93 is always
active but P89 is only active during motor starting.)
94
(for 2nd param set)
The time allowed for an overload condition before tripping.  For 60
Hz, 60 cycles = 1second. For 50 Hz, 50 cycles = 1second.
95
User Flags 1 (for 2nd param set)
Note that these bits operate with P96 bit 6 (param group selector).
This lets you set a primary and secondary group value.
Definition (Preset Value)
Bit0=  Kickstart 2 (0, Off)
Bit1= Current limit selector 2 (1, On)
Bit2= Overload selector 2 (1, On)
Bit3= Shearpin selector 2 (0, Off)
Bit4= Low current selector 2 (0, Off)
Bit5= Thermistor selector 2 (0, Off)
Bit6= Unused
Bit7= Remote starting 2  (1=P96 Bit4)  (If 0, 0=P96 Bit 3)
96
User Flags 2 (for 2nd param set)
Definition (Preset Value)
Bit0=  Low voltage Softstop (0, Off)
Bit1= Not global enable 1(2) (0, Off)
Bit2= Not global enable 2(2) (0, Off)
Bit3= Keypad Start/Stop 2 (0, Off)- (Available when P95 Bit7=1)
Bit4= Remote Start/Stop (0, Off)- (Available when P95 Bit7=0)
Bit5= Main contactor 2 (0, Off)- (use with a relay)
Bit6= Second Parameter Set 2 (1, On= Group 2)
Bit7= Zero Start time 2 (0, Off)
97
Flag1 I/P Source Address
Address of source flag parameter. 
(Parameter 98 is the mask for P97.)
98
Flag1 I/P Source Mask
The bit mask for source flag parameter.
99
Flag1 O/P Destination Address
Address of destination flag parameter. 
(Parameter 100 is the mask for P99.)