Toshiba E6581830 Manual Do Utilizador

Página de 51
 
E658130 
- 39 - 
6.2. 
Program example for setting the operation mode 
Example 2 shows 
a ladder logic to 
write data in the inverter.   
The operation mode of station 1 inverter can be changed to network operation. 
Operation mode writing code number: 2003H (hexadecimal) 
Network operation set data: 0004H (hexadecimal) 
The reply code at the time of instruction code execution is set to D2. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Check the ready of the station 1 
Write operation mode write code 
(2003H) to RWw2 and set data 
(0004H) to RWw3. 
X0 
X0F X1 
( M0) 
SW80.0 
M0 
X20 
[ PLS  M300] 
M300 
[ SET  M301] 
M301 
X100F 
[ MOV  H2003  W102]
[ MOV  H0004  W103]
[ SET  Y100F] 
[ RST  M301] 
[ SET  M302] 
M302 
X100F 
[ MOV    W2    D2]
[ RST  Y100F] 
[ RST  M302] 
[ END] 
Turn on the instruction code 
execution  
Read reply code (RWr2) to D2 when the   
Instruction code execution completion 
flag 
Turn off the instruction code 
execution  
Example