Toshiba E6581830 Manual Do Utilizador

Página de 51
 
E658130 
- 50 - 
3. Communication stops during operation 
▪ Check that the CC-Link units and the CC-Link dedicated cable are connected properly.   
(Check for contact fault, break in the cable, etc.)   
▪ Check that the PLC program is executed properly.   
▪ Check that data communication has not stopped due to an instantaneous power failure, etc. 
 
LED Status 
CCL003Z 
Master 
Station 
1 Station 
2 Station 
Cause Corrective 
Action 
L.RUN 
○ 
L.RUN 
● 
L.RUN
SD 
* 
SD 
● 
SD 
RD 
● 
RD 
● 
RD 
L.ERR 
○ 
L.ERR 
○ 
L.ERR
The station numbers of 
station 1 and 3 are   
duplicated. 
After correcting the   
repeated station   
numbers of the inverters, 
switch power on again. 
L.RUN 
● 
L.RUN 
○ 
L.RUN
SD 
● 
SD 
○ 
SD 
RD 
● 
RD 
● 
RD 
L.ERR 
○ 
L.ERR 
○ 
L.ERR
The baud rate setting of   
station 2 is different   
from master unit. 
After correcting the Baud 
rate setting, switch   
power on again. 
L.RUN 
● 
L.RUN 
● 
L.RUN
SD 
● 
SD 
● 
SD 
RD 
● 
RD 
● 
RD 
TIME○ 
LINE○ 
or 
TIME● 
LINE○ 
L.ERR 
○ 
L.ERR 
○ 
L.ERR
The setting data of   
station 3 was changed 
during normal   
operation. 
After returning the setting   
switch to the correct   
position, power on the   
inverter again. 
L.RUN 
● 
L.RUN 
● 
L.RUN
SD 
● 
SD 
● 
SD 
RD 
● 
RD 
● 
RD 
L.ERR 
○ 
L.ERR 
● 
L.ERR
Station 2 is affected by 
noise. (L.RUN may put 
out the light.) 
Securely connection FG 
of each inverter and   
master to ground. 
L.RUN 
● 
L.RUN 
● 
L.RUN
SD 
● 
SD 
● 
SD 
RD 
● 
RD 
● 
RD 
L.ERR 
○ 
L.ERR 
● 
L.ERR
the communication   
cable between the   
inverters of stations 2   
and 3 are affected by   
noise. (L.RUN may put 
out the light.) 
Check that the   
communication cable is 
connected to SLD.   
Also wire it as far away 
as   possible  from the 
power lines.(200mm or   
more) 
L.RUN 
● 
L.RUN 
● 
L.RUN
SD 
● 
SD 
● 
SD 
RD 
● 
RD 
● 
RD 
TIME● 
LINE● 
or 
TIME○ 
LINE● 
L.ERR 
○ 
L.ERR 
○ 
L.ERR
Terminal resistors are 
left un-connected.   
(L.RUN may put out   
the light.) 
Check that the terminal 
resistors are connected.
:
On, 
○:
OFF,  ◎:
Flicker, 
*:
 Any of on, flicker or off.
 
 
- 50E -