Campbell Hausfeld SDM-CD16AC Manual Do Utilizador

Página de 22
SDM-CD16AC 16 Channel AC/DC Controller 
Input Location assignments are as follows: 
Input 
Location 
Location 
Label 
 
Description 
1..5 
Temp #1..#5 
Avg temp, greenhouse 1..5 
10..14 
Heat #1..#5 
Heater control, greenhouse 1..5 SDM-CD16AC 
Port 1..5 
15..19 
Cool #1..#5 
Cooler control, greenhouse 1..5 SDM-CD16AC 
Port 6..10 
20..24 
Fan #1..#5 
Fan control, greenhouse 1..5 SDM-CD16AC  
Port 11..15 
 
1:  Beginning of Loop (P87) 
Master Loop, End 
 1:  0 
 Delay 
 
Loop at Step 30 
 2:  5 
 Loop 
Count 
 
 
START HEATER CONTROL LOGIC 
 
2:  If X<=>F (P89)   
If "Heater On" 
 1:  1-- 
 X 
Loc 
 
threshold is 
 2:  4 
 < 
 
exceeded 
 3:  23.5 
 F 
 
 4:  30 
 Then 
Do 
 
Then 
 
3:  Z=F (P30) 
   
Put a "1" into Heater 
 1:  1 
 F 
 
Control Location 
  2:  0 
  Exponent of 10  
  3:  10-- 
  Z Loc :  
 
4:  End (P95) 
   
End Then Do/End 
 
5:  If X<=>F (P89)   
If Heater 
 1:  10-- 
 X 
Loc 
 
#1 on (Heater Control 
 2:  2 
 <> 
 
Location <> 0) 
 3:  0 
 F 
 
 4:  30 
 Then 
Do 
 
Then 
 
6:  If X<=>F (P89)   
 
 1:  1-- 
 X 
Loc 
 
Temp #1 Check Upper Threshold 
 2:  3 
 >= 
 
to see if heater should 
 3:  25.5 
 F 
 
be turned off 
 4:  30 
 Then 
Do 
 
 
7:  Z=F (P30) 
   
If heater should be turned 
 1:  0 
 F 
 
off, enter a "0" into  
  2:  0 
  Exponent of 10  
heater control location 
  3:  10-- 
  Z Loc :  
 
8:  End (P95) 
   
Else Then Do/End 
 
12