4.2  Output Device Connections 
For each output channel there are four terminals which are labelled V
o
, Id plus 
there are two ground (
) connections per channel.  The two ground terminals 
are internally connected; two are provided for convenience. 
4.2.1  Voltage Output Mode 
The V
o
 terminal is the output for either the preset voltage signal, when the channel 
is set to operate in voltage mode or an unregulated 15 VDC power source in 
current mode. 
In voltage mode the connection to a remote device is a simple two wire 
connection: 
+
Inputs
 Remote Voltage Input
CVO4
V
o
 
4.2.2  Current Output Mode 
The Id terminal acts as the input for the current that is to be controlled. In current 
output mode you arrange to sink current into the terminal with a positive current 
flowing relative to the ground terminals. (In voltage output mode this terminal has 
no function.) 
There are several different possible connections in current mode. As each channel 
is isolated and floating, the method of connection to a remote device is flexible. 
There are two different ways of powering the loop current.