SDM-CVO4 4-Channel Current/Voltage Output Module 
 
Table 4-2.  Switch Position and Addresses 
Switch Setting 
Base 4 Address 
0 00 
1 01 
2 02 
3 03 
4 10 
5 11 
6 12 
7 13 
8 20 
9 21 
A 22 
B 23 
C 30 
D 31 
E 32 
F 33 
 
Use a screwdriver to select address
 
Figure 4-4.  Address Selection Switch 
The address switch has a hexadecimal setting position (0..F). Most datalogger 
instructions require you to enter the address as a base 4 number.  Please see your 
datalogger manual for more details of the convention required. 
4.5  Safety Considerations 
Where the potential voltage difference between the datalogger and the  
SDM-CVO4 outputs is considered to be non-hazardous (less than 50 V) then the 
unit can be used as any other peripheral without undue concerns as to the risks to 
safety of the user.  
As with the datalogger, it is essential to ensure that the device has a good 
connection to an earth grounding point to allow the safe discharge of any transient 
voltages and also ensure proper screening of the device. The  
SDM-CVO4 has two G terminals on the black connector which are used for 
connections to the datalogger. One of these can be used to connect the device 
directly to the earth ground point of the enclosure to ensure the lowest resistance 
path to ground. 