Toshiba H9 Manual Do Utilizador

Página de 289
H9 ASD Installation and Operation Manual
23
RX
 — The default function assigned to this terminal is the Torque Command setting. The RX terminal 
accepts a ±10 VDC input signal that is used to carry out the function assigned to this terminal. This 
input terminal may be programmed to raise or lower the speed or torque of the motor via an amplitude 
setting or this terminal may be used to regulate the speed or torque of a motor by setting a limit. The 
gain and bias of this terminal may be adjusted for application-specific suitability (see 
). See 
 for an electrical depiction of the RX terminal. This terminal references CCA.
V/I
 (I) — The function of the input is to receive a 0 – 20 mA input signal that controls a 0 – 80 Hz 
output. This is an isolated input terminal. This terminal is identified as V/I on the terminal board and 
may be programmed to control the speed or torque of the motor. This terminal cannot be used when 
using the input function. SW301 must be set to I to receive a current input signal at this terminal and 
is the default setting from the factory (see 
). This terminal references IICC. Scaling 
of the V/I terminal is accomplished via 
. The gain and bias of this terminal may be adjusted 
for application-specific suitability (see 
 and 
V/I
 (V) — The function of the V input terminal is to receive a 0 – 10 VDC input signal that controls a 
 
0 – 80 Hz output. This is an isolated input terminal. This terminal is identified as V/I on the terminal 
board and may be programmed to control the speed or torque of the motor. This terminal cannot be used 
when using the input. SW301 must be set to V to receive a voltage input signal at this terminal (see 
). This terminal references IICC. Scaling of the V/I terminal is accomplished via 
. The gain and bias of this terminal may be adjusted for application-specific suitability 
 and 
).
SU+
 — Externally supplied +24 VDC ± 10% @ 1.1 A (minimum) backup control power. This terminal 
references CC.
P24
 — +24 VDC @ 200 mA power supply for customer use. This terminal references CCA.
PP
 — The function of output PP is to provide a 10 VDC/10 mADC output that may be divided using a 
potentiometer. The tapped voltage is applied to the RR input to provide manual control of the RR 
programmed function. This terminal references CCA.
O1A/B
 (OUT1A/B) — The default function assigned to this terminal is Output Low Speed. This 
output may be programmed to provide an indication (open or closed) that any 1 of the functions that are 
listed in 
 has taken place. This function may be used to signal external equipment or 
to activate the brake (see 
). The OUT1 terminal is rated at 2 A/120 VAC and 2 A/30 VDC.
O2A/B
 (OUT2A/B) — The default function assigned to this terminal is ACC/DEC Complete. This 
output may be programmed to provide an indication (open or closed) that any 1 of the functions that are 
listed in 
 has taken place. This function may be used to signal external equipment or 
to activate the brake (see 
). The OUT2 terminal is rated at 2A/120 VAC and 2A/30 VDC.
FP
 — The default function of this output terminal is to output a series of pulses at a rate that is a 
function of the output frequency of the ASD. As the output frequency of the ASD goes up so does the 
FP output pulse rate. This terminal may be programmed to provide an output pulse rate that is 
proportional to any one of the items listed in 
. For further information on this terminal 
see 
AM
 — This output terminal produces an output current that is proportional to the magnitude of the 
function assigned to this terminal. The available assignments for this output terminal are listed in 
. For further information on this terminal see 
FM
 — This output terminal produces an output current or voltage that is proportional to the magnitude 
of the function assigned to this terminal. The available assignments for this output terminal are listed in 
. For further information on this terminal see 
. The Voltage/Current 
output selection is performed at 
SU+
P24
PP