H9 ASD Installation and Operation Manual
FLC
 — FLC is the common leg of a single-pole double-throw form C relay. The FL relay is the Fault 
Relay by default, but may be programmed to any one of the conditions listed in 
. For 
further information on this terminal see 
and
.
FLB
 — The normally-closed leg of the FL relay.
FLA
 — The normally-open leg of the FL relay.
Note:
The FLA, FLB, and FLC contacts are rated at 2A/120 VAC and 2A/30 VDC.
Figure 8. FLA, FLB, and FLC switching contacts shown in the de-energized state.
Figure 9. Terminal Board.
 Sink Source
See the section titled 
 for terminal descriptions.
See the section titled 
 for information on the proper 
cable/terminal sizes and torque specifications when making Terminal Board connections.
FLC
FLB
FLA
Note:
The relay is shown in the Faulted or de-energized condition. 
During normal system operation the relay connection is FLC-
to-FLA.
J101
TB1
TB2
TB3
J100
SW200
TB4
SW301
RE
S
CC
F
R
S1
S2
S3
S4
CC
ST
FP
+S
U
Ensure that the ground screw is securely in place to 
prevent arcing, intermittent operation, or system 
failure.
1 to 2 = Sink
2 to 3 = Source
1 to 2 = System Supplied
2 to 3 = Ext. Supplied
(24V)
V/I Switch
See 
 for more information on the Terminal Board connections.
Half/Full Duplex Switch
CAUTION
S4
RS485 4-Wire Communication