42
H9 ASD Installation and Operation Manual
EOI Command Mode
The EOI Command mode is accessed by pressing the ESC key from the Frequency Command screen.
The control settings of the EOI Command menu are effective for EOI control only.
The EOI Command mode provides quick access to the following menu parameters:
Direction
 — Forward or Reverse.
Stop Pattern
 — The Decel Stop or Coast Stop settings determines the method used to stop the 
motor when using the Stop|Reset key of the EOI. The Decel Stop setting enables the Dynamic 
Braking
 system setup at 
 or the DC Injection Braking system setup at 
, an
The Coast Stop setting allows the motor to stop at the rate allowed by the inertia of the load.
Note:
The Stop Pattern setting has no effect on the Emergency Off settings of 
V/f Group
 — 1 of 4 V/f profiles may be selected and run. Each V/f profile is comprised of 4 user 
settings: Base FrequencyBase Frequency VoltageManual Torque Boost, and Electronic 
Thermal Protection
. Expanded descriptions of these parameters may be found in the section titled 
.
Accel/Decel Group
 — 1 of 4 Accel/Decel profiles may be selected and run. Each of the Accel/
Decel profiles is comprised of 3 user settings: AccelerationDeceleration, and Pattern. Expanded 
descriptions of these parameters may be found in the section titled 
 (or see 
Feedback in Panel Mode
 — This feature enables or disables the PID feedback function.
Torque Limit Group
 — This parameter is used to select 1 of 4 preset positive torque limits to apply 
to the active motor (of a multiple motor configuration). The settings of profiles 1 – 4 may be setup at 
, and 
, respectively.