Toshiba H9 Manual Do Utilizador

Página de 289
H9 ASD Installation and Operation Manual
43
Monitor Mode
The Monitor mode allows the user to monitor motor performance variables, control settings, and 
configuration data during motor operation. There are 43 items that may be monitored from this mode. The 
items are listed and described below.
Note:
The Monitor mode is a read-only mode. The settings cannot be changed from the 
Monitor mode. For information on how to change the values, see the section titled 
Note:
Any two of the Underlined monitored items may be selected for display at the 
Frequency Command screen while running via Program 
⇒ 
Utilities
 ⇒
 
.
Note:
The 
 setting will determine if the Current and Voltage values displayed appear 
as A (Amps) or V (Voltage), or if the value is shown as a
 %
 (percentage) of the ASD 
rating.
Frequency at Trip
 — Display the at-trip frequency.
Frequency Reference
 — Displays the Frequency Setpoint (also called the Commanded 
Frequency).
Output Current
 — Displays the Output Current as a percentage of the rated capacity of the H9 
ASD.
DC Bus Voltage
 — Displays the Bus Voltage as a percentage of the rated capacity of the H9 ASD.
Output Voltage
 — Displays the Output Voltage as a percentage of the rated capacity of the H9 
ASD.
AM Output
 — Displays the AM output terminal value for the function assigned to the AM terminal.
FM Output 
 Displays the FM output terminal value for the function assigned to the FM terminal.
Motor OL (Overload) Real
  Displays the real-time Motor Overload value as a percentage of 
the rated capacity of the motor.
Motor OL (Overload) Trip
  Displays the Motor Overload Trip value as a percentage of the 
rated capacity of the motor.
Motor Load
 — Displays the real-time Motor Load as a percentage of the rated capacity of the 
motor.
ASD OL (Overload) Real
 — Displays the real-time ASD Overload as a percentage of the rated 
capacity of the H9 ASD.
ASD OL (Overload) Trip
  Displays the ASD Overload Trip value as a percentage of the rated 
capacity of the ASD.
ASD Load
 — Displays the ASD Load as a percentage of the rated capacity of the H9 ASD.
Run Time
 — Displays the Cumulative Run Time in hours.
Compensation Frequency
 — Displays the Output Frequency after the application of the slip 
compensation correction value (Post Compensation Frequency).
DBR OL (Overload) Real
 — Displays the real-time DBR Overload value as a percentage of the 
Dynamic Braking Resistor capacity.
DBR OL (Overload) Trip
 — Displays the DBR Overload Trip value as a percentage of the 
Dynamic Braking Resistor capacity.
DBR Load
 — Displays the DBR Load as a percentage of the Dynamic Braking Resistor capacity.
Feedback (inst) 
— Provides a status of the Real Time Feedback in Hz.
Feedback (1 second)
 — Provides a status of the 1-Second Averaging feedback in Hz.