Grounding method
The method of grounding used for the Option 11C Mini depends on whether 
the same service panel powers all chassis.
The following three grounding scenarios are possible:
1
A system with one chassis
2
A system with more than one chassis, powered by the same service panel
3
A system with more than one chassis, powered by different service 
panels
A system with one chassis or multiple chassis powered by one 
service panel
For each Main Chassis, connect a #6 AWG (#40 Metric Wire Gauge) ground 
wire from the chassis to the NTBK80 grounding block. See Table 10 on 
page 49
 for grounding wire requirements specific to some areas. Connect the 
grounding block to a ground source (the ground bus in the AC power service 
panel).
Consider the Main Chassis and the Chassis Expander as the same ground. 
Jumper the ground wire from the Chassis Expander to the Main Chassis and 
then back to the grounding block.
CAUTION
To prevent ground loops, power all chassis from the same dedicated 
power panel. Ground all Main Chassis to the power panel through the 