 Chapter 3 — System and site requirements
Page 55 of 332
Option 11C Mini
Planning and Installation Guide
Commercial power requirements
The Option 11C Mini system is available with AC-power only.
The optimal installation of the AC-powered Option 11C Mini system 
includes a direct connection to the electrical system in the building, provided 
some requirements are met. Refer to AC-powered installation later in this 
chapter for detailed information. The Main Chassis and Chassis Expander can 
share the same electrical breaker.
You can use an approved isolation transformer for AC-powered systems 
when meeting the optimum requirements is not possible or is too expensive. 
See “Alternative AC-powered installation” on page 58.
Refer to “Power consumption worksheets for the Option 11C Mini system” 
on page 64 to
 determine the power consumption of the Option 11C Mini.
AC power installation for systems installed on a wall or table
Use a dedicated AC service panel with the Option 11C Mini system. Do not 
connect equipment that is not related to the Option 11C Mini to this panel. 
Keep all lighting, fans, motors, air conditioning equipment, and the like, as 
“electrically separate” from the Option 11C Mini system as possible. The 
Main Chassis and Chassis Expander can share the same AC breaker.
AC power installation for systems installed in a rack/cabinet
If other data communications equipment is in the same rack/cabinet as the 
Option 11C Mini, power each piece of equipment from an isolated ground 
outlet. The same service panel must service all outlets. 
Power from each outlet must meet the input requirements of at least one 
Option 11C Mini power supply, as listed in Tables 11 through 13. Check 
power requirements for other system equipment. Install additional outlets if 
you need to.