 Chapter 3 — System and site requirements
Page 57 of 332
Option 11C Mini
Planning and Installation Guide
Site requirements
The following is a list of required site features for an optimal Option 11C 
Mini AC-powered system installation. 
If a dedicated panel cannot provide the conditions listed below, use an 
Isolation Transformer. Refer to “Alternative AC-powered installation” on 
page 58.
Dedicated circuit breaker panel
A dedicated circuit breaker panel provides power only to the Option 11C 
Mini system and its related hardware, such as TTYs and printers
Note: You can
 
not always power a complete system from a single 
circuit-breaker panel. For example, when chassis are located remotely.
Insulated copper ground conductor
Insulated copper ground conductor connects the ground bus in the 
dedicated panel to the main service panel ground or building ground 
reference. Route the insulated copper ground conductor through the 
same conduit as the supply conductors that feed the panel.
Isolated-ground receptacles
All outlets connected to the dedicated panel must be of the isolated 
ground type. Use a separate circuit for each device connected to the 
panel. Outlets that provide service to the chassis must be close enough so 
that the power cord can reach the chassis power supply.
Isolated ground bus in the electrical panel, where permitted by local 
codes
Table 13
AC input requirements for each NTDK91 and NTDK92 (Germany)
Voltage
Recommended: 230 volts
Maximum limits: 180 and 250 volts
Single phase
Frequency
50 Hz
Power 
(I/P max)
550 VA maximum
Fuse
16A
Outlet Type
Receptacles by DIN regulation