Third Party Protocols
 ION 7500 / ION 7600 User’s Guide
Page 68
Chapter 3 - Default Meter Functionality 
Third Party Protocols
Modbus and DNP modules are factory configured and do not require basic 
configuration changes. Changing the factory configuration is an advanced setup 
procedure that requires an understanding of the protocol, as well as an 
understanding of the meter’s internal operation.
Refer to the technical notes DNP 3.0 and ION Technology, and Modbus and ION 
Technology
 for the appropriate list of parameters available for each protocol. 
N
OTE
The meter can also be configured to receive data through Modbus or DNP 3.0, though there is no factory-
configured framework for receiving data through these protocols. For details on configuring your network
for receiving data via Modbus or DNP 3.0, refer to the DNP Slave Import module and Modbus Slave
Import module descriptions in the online
 ION Programmer’s Reference
, as well as the technical notes
DNP 3.0 and ION Technology,
 and 
Modbus and ION Technology
.
Communications Protocol Configuration
In order to use the factory Modbus or DNP configuration you must first configure 
the communications channel you want to use. By default, all communications 
ports are configured to use the ION protocol. Choose the 3rd-party protocol you 
want from the list of available protocols in the Communications module’s Protocol 
setup register. 
N
OTE
Modbus RTU is available on each of the meter’s communications ports, and multiple ports can
communicate using Modbus simultaneously. Only a single port can use the DNP 3.00 protocol at any
one time.