Using the Modbus RTU Protocol
 ION 7500 / ION 7600 User’s Guide
Page 70
Chapter 3 - Default Meter Functionality 
Modbus Slave Module Settings
The settings in the Modbus Slave module setup registers are shown in the tables 
below. Refer to ION 7500 / ION 7600 Series meter Modicon Modbus Serial 
Communications Protocol and ION/Modbus Register Map 
document for additional 
details on the Modbus implementation on the meter.   
Modbus Slave Module #1
Modbus Slave Module #2
Setup Register
Setting
Setup Register
Setting
Format
unsigned 16-bit
Format
signed 32-bit
Base Address
40011
Base Address
40027
Scaling
YES
Scaling
YES
In Zero
0
In Zero
-214748364
In Full
6553
In Full
214748364
Out Zero
0
Out Zero
-2147483640
Out Full
65530
Out Full
2147483640
Modbus Slave Module #3
Modbus Slave Module #4
Setup Register
Setting
Setup Register
Setting
Format
signed 32-bit
Format
signed 32-bit MFP
Base Address
40059
Base Address
40089
Scaling
YES
Scaling
NO
In Zero
-214748364
In Full
214748364
Out Zero
-2147483640
Out Full
2147483640
Modbus Slave Modules #5 to #15 (EN50160 data)
Setup Register
Setting
Setup Register
Setting
Base Addresses
#5: 41000
Format
unsigned 16-bit
#6: 41016
Scaling
NO
#7: 41032
In Zero
-32767
#8: 41048
In Full
 32767
#9: 41064
Out Zero
-32767
#10: 41080
Out Full
 32767
#11: 41096
#12: 41112
#13: 41128
#14: 41144
#15: 41160