Install Equipment Room Hardware
Issue 10 June 2005
65
 
Figure 22: Model 507B Sneak Fuse Panel
Approximately 8 inches (20 cm) of horizontal wall space is required for each column of sneak 
fuse panels. Connector cables connect the network interface to the sneak fuse panel. Also, use 
157B connecting blocks equipped with SCP-110 protectors for sneak current protection.
Note:
Note:
Sneak current protectors with a rating of 350 mA at 600 V must be UL listed for 
United States installations and CSA certified for Canadian installations. The 
panel contains two 25-pair connectors, fuse removal tool, and fifty 220029 Sneak 
Fuses (and 2 spares). Use the SCP-110 protectors with 110-type hardware and 
on the 507B Sneak Fuse Panel. The SCP-110 Protectors can be ordered 
separately and installed on the 157B connecting block. Fifty protectors are 
required per block.
To install sneak fuse panels:
1. Install the 507B near the network interface or MDF with locally-obtained #12 x 3/4-inch 
screws (or equivalent).
Figure notes:
1. Sneak current protector (PEC 63210)
2. 25-pair male connector (In)
3. 25-pair female connector (Out)
4. 220029 fuses (inside panel). Use a small 
screwdriver to pry top cover off
Sneak
Current
Protector
507B
sneak CJL 032096