− 10 − 
 
5.2 Control Panel and Indicators 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Functions 
No. 
Label 
Status display 
Lit 
Not lit 
Slow blink 
Fast 
blink 
LED0 INPUT Input power status 
Normal input 
 
Input error 
 
LED1 
OUTPUT  UPS output power status  Inverter operation  OFF 
Bypass operation 
 
LED2 ECONOMY Operation 
mode 
Economy mode 
operation  (*1) 
OFF (*3) 
 
 
LED3 
DOUBLE 
CONVERSION  Operation mode 
Double conversion 
mode operation (*2)  OFF (*3) 
 
 
LED4  BATT.LOW  Battery status 
Battery power low  Battery power 
normal 
Battery exhausted 
 
Load level 25% 
Load 25% or more  Load under 25% 
 
 
LED5 25 
Output voltage setting 
100V (*4) 
 
Setting other than 
100V 
100V setting (*4) 
 
Load level 50% 
Load 50% or more  Load under 50% 
 
 
LED6 50 
Output voltage setting 
110V (*4) 
 
Setting other than 
110V 
110V setting (*4) 
 
Load level 75% 
Load 75% or more  Load under 75% 
 
 
LED7 75 
Output voltage setting 
115V (*4) 
 
Setting other than 
115V 
115V setting (*4) 
 
Load level 100% 
Load 100% or more  Load under 100% 
 
 
LED8 100 
Output voltage setting 
120V (*4) 
 
Setting other than 
120V 
120V setting (*4) 
 
LED9 
L
O
ADL
E
VEL
(%
O.L. 
Overload display 
Load 105% or more  Load under 105% 
None 
 
LED10 ALARM Alarm display 
Failure detected 
No failure 
 
 
 
INV.ON 
STAND BY  Inverter operation On/Off operation 
LED11 
INV.ON 
STAND BY  Inverter operation status  Inverter operation 
Off Bypass 
operation 
 
 
BATT.TEST Battery test 
LED12 BATT.TEST Battery test 
Result: Normal 
 
Result: Error 
Status: 
Testing 
 
CLEAR 
Stop buzzer, clear result of battery test 
 
1. Economy mode operation・・・・When power conditions are good, UPS supplies this power to the load. 
2. Double conversion mode operation・・・・When power conditions fluctuate, UPS converts to the stable power, and 
supplies to the load. 
3. Active Filter Mode operation・・・・When load power fluctuates. Suppresses high frequencies generated by the load 
and improves power factor.   
When the green DOUBLE CONVERSION and the green ECONOMY are both off, the UPS is in Active Filter Mode. 
4. The output voltage setting is displayed for about 5 seconds after the UPS is powered on (LED initialization display). 
 
This manual uses a frame                to indicate switches. (Example:    INV.ON/STAND BY    ). 
It also describes the color of the LED whenever it refers to an indicator on the control panel. 
(Examples: Green INV.ON/STAND BY, red ALARM) 
 
 
 
 
 
 
LED6
LED10 
LED11 
LED9
LED4 
LED0 LED1 LED2 LED3 
LED7
LED8
LED12
LED5 
 
 
 
: Indicates a lit LED 
In the illustrations in this manual 
: Indicates a blinking LED