Sanyo E11A202U Manual Do Utilizador

Página de 47
 
− 12 − 
 
6. Installation 
 
 
CAUTION 
 
 
・ 
When installing the UPS, carefully follow the instructions in this Instruction Manual. 
・ 
Install the UPS on a stable surface that can bear the weight (29 kg, 63.93 lbs). 
This surface should be flat, so the UPS cannot fall and cause bodily injury. 
・ 
The possibility of vibration and shock should be minimized at the installation location. 
・ 
All work that involves lifting the UPS, such as mounting it in a rack or attaching the 
stand, should be carried out by at least 2 persons. 
・ 
Be careful to avoid straining your lower back when moving and installing the UPS. 
・ 
There is a danger that the UPS could fall or be dropped during relocation or 
installation. Always hold the UPS securely by the upper edges. Failure to do so can 
result in bodily injury or damage to the UPS. 
 
6.1 Environment 
Do not install the UPS in the following locations: 
•  Where the ambient temperature exceeds 40°C (104°F). 
For optimum battery life, install the UPS where the ambient temperature remains 
between 20 to 25
°
C (68 to 77
°
F). 
•  Where high humidity may occur. 
•  Where corrosive gas or salt spray may be present. 
•  Where it may be subject to vibration and shock. 
•  Where dust may accumulate. 
•  In a poorly ventilated rack (when the UPS is rack mounted). 
 
6.2 Transporting 
Transport the UPS in its original packing   
carton, removing it only when near the   
installation location. 
 
6.3 Installation Space 
During installation, provide the following space around the UPS. 
•  At least 20 cm (about 8 inches) at the front as air intake space for cooling. 
•  At least 20 cm (about 8 inches) at the back as air exhaust space for cooling 
•  At least 1 meter (about 40 inches) at the front and 50 cm (about 20 inches) at the back 
for maintenance when needed. 
•  At least 1 meter (about 40 inches) from CRT displays to allow for slight leakage of 
magnetic flux. Allow some space from devices which might be affected by magnetic 
flux. 
 
Installation Space for Vertical or Horizontal Installation        Installation Space for Rack Mounting 
 
 
 
Intake space
E11A 
Exhaust space 
At least 20cm   
(Back)
(Front)
Rack
Maintenance space 
At least 1m (40 in) 
Maintenance space 
At least 50 cm (20 in)
At least 20cm
(8 in)
(8 in)
 
Exhaust spac
 
At least 
20cm (8 in) 
At least 1m (40 in) 
At least 
20cm (8 in) 
Intake space 
Maintenance space 
At least 50 cm (20 in)
Maintenance space 
E11A
 
(Back) 
 
Front 
Exhaust space 
 
CAUTION 
 
 
When moving the UPS, do not let it tilt 
more than 10 degrees to either side. 
Tilting of more than 10 degrees can 
cause the UPS to fall, resulting in 
bodily injury. 
If you must tilt the UPS more than 10 
degrees, be careful not to let it fall.
 
The rack that 
there are 
ventilation 
holes in the 
door is 
recommended.