Installation Procedures: Connect User Contact Inputs and Output Relays to the User Connection Plate
18
InfraStruXure Site Planning, Installation, Start-Up
How to connect contacts to the PDU Monitoring Unit
To connect and monitor your contacts:
1. Choose the numbers of the contacts to which you will connect.
2. From the PDU display interface:
a. Press the 
E
SC
 or 
E
NTER
 key to go to the top-level menu screen.
b. Select Contacts on the top-level menu screen and press the 
E
NTER
 key.
c. Press the 
E
NTER
 key to select the number of the contact you are connecting. The continue 
arrow   will appear next to the contact number.
d. Press the Up or Down arrow key to select the appropriate contact number and press the 
E
NTER
 
key.
e. Press the Down arrow key to enter a unique Name for the contact and to configure the 
Normal state of the contact (Open or Closed). The default Normal state is Open. Press the 
E
NTER
 
key to select the item you wish to configure.
3. Connect contact wires (300V-rated cabling required) to the terminal block on the user 
connection plate. You will need a 2.5-mm standard screwdriver.
4. Run the wires from the terminal block out the roof or under the floor of the PDU to your 
contact’s location.
You will be prompted for your password to configure these items.
Ensure that wires are properly retained and away from high voltage lines 
and breakers.