Chapter 4 Troubleshooting
209418-A
Normal power-up sequence
In a normal power-up sequence, the LEDs appear as follows:
1
After power is applied to the switch, the Pwr (Power) LED turns on within 5 
seconds.
2
The switch initiates a self-test, during which the port LEDs display various 
patterns to indicate the progress of the self-test.
3
After the self-test, the remaining port LEDs indicate their operational status, 
as described in 
.
Avvertenza: Per evitare lesioni fisiche dovute a scariche pericolose di 
corrente, non rimuovere mai il coperchio superiore del dispositivo. I 
componenti interni non possono essere manipolati dall’utente.
 
Table 43   Corrective actions
Symptom
Probable cause
Corrective action
All LEDs are off.
The switch is not receiving AC 
power.
Verify that the AC power cord is fastened 
securely at both ends and that power is available 
at the AC power outlet.
The fans are not operating or 
the airflow is blocked, causing 
the unit to overheat.
Verify that there is sufficient space for adequate 
airflow on both sides of the switch.
Note: 
Operating temperature for the 
switch must not exceed 40°C (104°F). Do 
not place the switch in areas where it can 
be exposed to direct sunlight or near 
warm air exhausts or heaters.