RuggedCom RS900GP Manual Do Utilizador

Página de 24
3. Specifications
RuggedCom® RuggedSwitch™
21
RS900GP Installation Guide Rev 100
3.7. Type Test Specifications
3.7.1. IEC 61850-3 Type Tests
Test
Description
Test Levels
Severity
Levels
Enclosure Contact
+/- 8kV
4
IEC 61000-4-2
ESD
Enclosure Air
+/- 15kV
4
IEC 61000-4-3
Radiated RFI
Enclosure ports
20 V/m
x
Signal ports
+/- 2kV @ 2.5kHz
x
D.C. Power ports
+/- 2kV
4
IEC 61000-4-4
Burst (Fast Transient)
Earth ground ports
+/- 2kV
4
Signal ports
+/- 2kV line-to-earth,
+/- 1.5kV line-to-line
4
IEC 61000-4-5
Surge
D.C. Power ports
+/- 1.5kV line-to-earth,
+/- 1kV line-to-line
3
Signal ports
10V
3
D.C Power ports
10V
3
IEC 61000-4-6
Induced (Conducted) RFI
Earth ground ports
10V
3
IEC 61000-4-8
Magnetic Field
Enclosure ports
40 A/m continuous,
1000 A/m for 1 s
N/A
IEC 61000-4-29
Voltage Dips & Interrupts
D.C. Power ports
30% for 0.1s, 60% for
0.1s, 100% for 0.05s
N/A
Signal ports
2.5kV common, 1kV
differential mode @ 1MHz
3
IEC 61000-4-12
Damped Oscillatory
D.C. Power ports
2.5kV common, 1kV
differential mode @ 1MHz
3
Signal ports
30V Continuous, 300V for 1s
4
IEC 61000-4-16
Mains Frequency Voltage
D.C. Power ports
30V Continuous, 300V for 1s
4
IEC 61000-4-17
Ripple on D.C. Power Supply
D.C. Power ports
10%
3
Signal ports
1.5kV AC (Fail-
Safe Relay output)
N/A
IEC 60255-5
Dielectric Strength
D.C. Power ports
1.5kV DC
N/A
Signal ports
5kV (Fail-Safe Relay output)
N/A
IEC 60255-5
H.V. Impulse
D.C. Power ports
5kV
N/A
Table 3.9. RS900GP IEC 61850-3 Type Tests