RuggedCom RS900GP Manual Do Utilizador

Página de 24
3. Specifications
RuggedCom® RuggedSwitch™
22
RS900GP Installation Guide Rev 100
3.7.2. IEEE 1613 Type Tests
IEEE Test
IEEE 1613 Clause
Description
Test Levels
Enclosure Contact
+/- 8kV
C37.90.3
9
ESD
Enclosure Air
+/- 12kV
C37.90.2
8
Radiated RFI
Enclosure ports
35 V/m
Signal ports
+/- 2kV
@ 2.5kHz
D.C. Power ports
+/- 2kV
C37.90.1
7
Fast Transient
Earth ground ports
+/- 2kV
Signal ports
2.2kV
common
mode @
1MHz
C37.90.1
7
Oscillatory
D.C. Power ports
2.2kV
common &
differential
mode @
1MHz
Signal ports
5 kV (Failsafe
Relay)
C37.90
6
H.V. Impulse
D.C. Power ports
5 kV
Signal ports
2kV
AC(Failsafe
Relay)
C37.90
6
Dielectric Strength
D.C. Power ports
1.2kV DC
Table 3.10. RS900GP IEEE 1613 Type Tests
• If  the  unit  contains  copper  ports  the  IEEE  1613  conformance  is  Class  1  (During
disturbance errors may occur but recovery is automatic).
• If  the  unit  contains  all  fiber  ports  the  IEEE  1613  conformance  is  Class  2  (During
disturbance no errors will occur).
3.7.3. IEC Environmental Type Tests
Test
Description
Test Levels
Severity Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40°C, 16 Hours
N/A
IEC 60068-2-2
Dry Heat
Test Bd
+85°C, 16 Hours
N/A
IEC 60068-2-30
Humidity (Damp
Heat, Cyclic)
Test Db
95% (non-condensing),
55°C, 6 cycles
N/A
IEC 60255-21-1
Vibration
2g @ (10-150) Hz
Class 2
IEC 60255-21-2
Shock
30g @ 11 ms
Class 2
Table 3.11. IEC Environmental Type Tests