NetVanta 1000/1000R Series Hardware Installation Guide
 Unit Installation
61200500L1-34N
Copyright © 2008 ADTRAN, Inc.
57
Figure 37.  Grounding the NetVanta 1224STR (DC)
Installing Dial Backup and Network Interface Modules
The DIM plugs on to the NIM. The NIM is then installed into the rear panel option module slot. The following 
tables list the installation steps. Also, see Figure 38 on page 58 and Figure 39 on page 59.
To comply with GR-1089-CORE, Issue 3, this equipment MUST only be installed in a 
DC-C (common) bonding and grounding environment. It may not be utilized in a DC-I 
(isolated) bonding and grounding environment.
For NetVanta modules with outside plant connections, ensure that all cables are 
removed from the module before installing or removing it from the NetVanta chassis.
Always remove power from the unit prior to removing or installing a module.
Improper installation may result in damage to the modules.