GE Energy Services 
BECCO2200 DCA  
Configuration Guide  
 
 
A164-0CG-1.00-2 Restricted 
 Full 
 
Table 1  BECO2200 DCA Configuration Tables 
1.2 Configuration 
Sequence 
The following is a list of the steps required to configure the BECO2200 DCA: 
1.  Edit the A164 configuration. Prepare it according to the guidelines in this document and the 
specific use for which the BECO2200 DCA is required. 
2.  Edit the configuration for all other applications that will run on the product. Prepare them 
according to their own configuration guides. 
3.  Generate the configuration and download it to the product using the GE Energy Services 
Configuration System provided. The list of applications to be compiled must include A164. 
4.  Restart the product. The BECO2200 DCA will check the validity of its configuration 
parameters and begin its initialization. If it determines that a configuration parameter is 
incorrect or encounters an error during its initialization, it will log a message to the 
WESMAINT Error Log and then, depending on the severity of the error, terminate or 
continue with its run-time function. Self-termination of the BECO2200 DCA prevents it from 
running using invalid data. 
5.  Check for error messages. Log into the WESMAINT maintenance interface, select the 
System Functions item from the Main Menu, and then select the Error Log item from the 
System Functions Menu. If any error messages are displayed, correct the problem as 
described in Appendix A: Messages Logged by the BECO2200 , and repeat steps 3 through 5. 
Configuration is complete when the BECO2200 DCA has successfully validated all 
configuration parameters.