Chapter 2: Configuring Win for the 
BECO2200 DCA  
This chapter describes how to configure the WESDAC Interface Node (WIN) for the BECO2200 
DCA. The application number for WIN is B008. Refer to the WIN User’s Configuration Guide 
for more information on how to configure WIN. The functionality of all points required by the 
BECO2200 DCA is defined in the BECO2200 DCA Functional Specification. 
2.1 WESDAC 
Point 
Allocation 
WESDAC data point allocation is accomplished by specifying the required number of points in 
the WIN configuration tables. Any points allocated to the BECO2200 DCA are maintained 
solely by the BECO2200 DCA. This means the BECO2200 DCA is the only application that 
may modify the value or the status of those points. All points allocated to the BECO2200 DCA 
are initialized to off-line and not communicating. If the WESDAC table is in NVRAM, points 
are initialized to the current value (state) in NVRAM. If the WESDAC table is in RAM, the 
points are initialized to zero (off). 
 
Number of points required 
WESDAC DATA TYPE 
BECO 2200 M-0420 
Binary Inputs 
42 
Binary Outputs 
44+MDPC 
Counters 38 
Analog Input 
281 
Analog Outputs 
78 
Device Status 
Table 2  Required Points BECO2200 Device