TROUBLESHOOTING (cont.)
Check for "ON" position or no con-
tinuity - replace switch.
Clean or replace condenser filter.
Replace  fan  motor  or  check  fan 
blades for obstructions.
Check  compressor  relay  coil  for 
120vac.
NOTE:  Aleays  check  power  with 
coil attached.If no 120vac - replace 
board.  If  yes,  120vac  -  replace 
relay.
Note:  Relay  contacts  normally 
open.
Check compressor thermal overload 
(N/C). If open check for dirty con-
denser filter or adequate ventilation 
and space around machine.
Check refrigeration system for leaks 
and proper charge.
See page 17 for instruction on how 
to reset or change password.
Check all previous items that pre-
tain to refrigeration or cold water 
recirculation
1. Compressor ON/OFF switch.
2. Dirty condenser filter or fins.
3. Condenser fan not running.
4.  Compressor  relay  not  activat-
ing.
5. Compressor not running.
6.  Compressor  running  and  not 
cooling.
1.  Dispenser  lockout  password 
set.
1. Refrigeration or cold water recir-
culation system.
Refrigeration
All dispense stations not working 
or all water & refill LED's flash and 
beep 3 times.
Note: Cooling failure or excessive 
bath and cabinet temperatures for 
m  ore  than  4  hours  will  result  in 
touchpad lockout or no dispense.
Dispenser Locked Out
All dispense stations not working 
or all water & refill LED's flash and 
beep 3 times.
Hint: Display light goes out during 
dispenser lockout feature, if the unit 
has lighted graphics.
Cooling  system  failure  or  DBC 
fault 3.
PROBLEM
PROBABLE CAUSE
REMEDY