Chapter 2: Functional Description 
12 of 90 

  Multiple refrigeration access ports 

  Liquid line shut-off ball valves 

  Filter-dryer 

  Sight glass 

  Externally equalized thermal expansion valve 

  Liquid line solenoid 

  Compressor crankcase heater 
Controller Features 

  Off-the-shelf microprocessor-based PID controller with To Process, From Process and 
Set Point readout 

  Time delay for proof of water flow/pressure (models w/pump only) 

  Low refrigerant pressure time delay for low ambient start-up on remote air-cooled and 
air-cooled chillers with the variable-speed fan option. 

  8 line x 22 character display with status, alarm, and service screens 

  Display has magnetic back and can be mounted anywhere. 
Other Features 

  One year labor warranty and one year compressor  warranty 

  Two year parts warranty 

  Three year limited controller warranty 
2-4  Safety Devices and Interlocks 
 
Caution!  Protect the system from freezing with inhibited industrial grade glycol 20ºF 
below the leaving water temperature set point. Condensation may form inside 
the pump tank and dilute the mixture, therefore the freezing point should be 
verified periodically. See Figure 6 on page 18 for the correct mixture.  
Crankcase Heater 
All of the chillers are equipped with a compressor crankcase heater. It is wired through the 
control transformer that operates continuously whenever power is applied to the chiller, and 
the compressors are off. 
Caution!  Energize the crankcase heater for at least 24 hours before initial startup to 
drive dissolved refrigerant from the compressor oil. Failure to do so will 
damage the compressor.  If unit is mounted outdoors, power to the unit (and 
the main power switch) must remain on 24 hours per day, 7 days per week to 
prevent liquid migration to the compressor.