GP Series Portable Chillers 
Chapter 2: Functional Description 
13 of 90 
High Pressure Cutout 
This electro-mechanical cutout device opens the compressor control circuit if the refrigeration 
system compressor discharge pressure exceeds 575 psig.  
Note: 
The high-pressure cutout is a manual reset device typically mounted on the 
compressor discharge line inside the mechanical cabinet. Call a refrigeration 
service technician to analyze the problem and reset the control.  
 
Typical GPAC-20 
Low Pressure Cutout (no switch but done through the transducer) 
There are two pressure transducers in the refrigeration piping – one on the suction line before 
the compressor and one on the discharge line after the compressor.  Within the program there 
are four settings that warn and fault based on these two pressure transducers.  The low suction 
pressure warning and fault are calculated based on the Freeze Point value entered into the 
controller.  The low discharge warning is set for 200 psig (1,379 kPa), and the compressor 
will fault at 180 psig (1,241 kPa).  To prevent nuisance tripping there are delays built in to the 
program. 
Note: 
Call a refrigeration service technician to analyze the problem to prevent 
recurring low pressure faults. 
 