Sterling 882.93092.01 Manual Do Utilizador

Página de 90
GP Series Portable Chillers 
Chapter 3: Installation 
16 of 90 
Chapter 3:   Installation 
3-1  Uncrating 
All models are shipped mounted on a skid, enclosed in a plastic wrapper, and open-crated on 
all four sides and top. 
1.  Pry the crating away from the skid. 
2.  Use a pry bar to remove the blocks securing the unit to the skid. 
3.  Lift unit from sides, inserting forklift under the base. The forks must be equidistant 
from the centerline of the unit and the unit must be balanced on the forks. Lift slowly 
and only high enough to clear the skid. Use a pry bar if necessary to carefully remove 
the skid from the unit. 
4.  Lower slowly. The unit should land on its casters or rails and can then be moved into 
position. 
5.  Retain the crating material for reshipping the chiller in case hidden shipping damage 
is found. 
 
3-2  Electrical Connections 
Supply electricity of the voltage, phase, and cycle listed on the serial tag. Total running amps 
are also found in the specification tables on pages in the Appendix. 
Bring properly sized power leads and ground from a fused disconnect (installed by your 
electrician) to the unit. Use dual-element fuses in the disconnect switch, sized according to 
the National Electrical Code recommendations. Make sure all electrical connections are tight.  
 
 
 
 
 
 
Note: 
For all chillers manufactured with Variable Frequency Drives the 
voltage may vary up to 10% from the converter nominal voltage.  
However, the phase-to-phase input voltage imbalance must not 
exceed 3%.  If the input voltage does have an imbalance from phase 
to phase greater than 3% then a line reactor must be installed to 
prevent faults within the VFD. 
 
For remote condenser units, the maximum recommended motor 
cable length between the VFD and the motor without output chokes 
is 30 m (100 ft).  With output chokes the motor cable length may be 
extended to 65 m (195 ft). 
 
Important! 
Refer to your local electrical requirements for proper feeder conductor and 
supply disconnecting sizing.  For instance, in the United States refer to 
National Electric Code (NEC) Article 430-24 through 430-26, Table 
310.15(B)(2)(a)