Chapter 3: Installation 
21 of 90 
Sizing Refrigerant Lines. To determine field installed liquid and discharge line sizes, first 
establish the equivalent length of pipe for each line, valve, and elbow. Chiller capacity and 
leaving water temperature range is also required. See Figure 4 on page 21 for lengths of 
refrigerant valves and fittings. 
Liquid Line Sizing. The liquid line should be sized as small as possible while maintaining 
acceptable pressure drop to minimize the refrigerant charge. Liquid line risers must not 
exceed 15 feet from the base of the air-cooled condenser. Horizontal runs do not require a 
pitch. Insulation is not required unless the line is installed in a high ambient area, i.e., boiler 
room or on a roof. Install a liquid line-charging valve to facilitate refrigerant charging. See 
Figure 5 on page 21 for sizing information. See Figure 7 on page 25 for charge determination. 
Discharge Line Sizing. Discharge line sizing is based on the velocity required for sufficient 
oil return back to the compressor. See Figure 4: Equivalent Length in Feet for Valves and 
Fittingson page 24 for discharge line sizing. 
Note: 
For horizontal runs, the discharge line should be pitched downward, in the 
direction of flow, at a rate of 1/2” for every 10 feet. This will allow oil to flow 
towards the condenser. 
Figure 4: Equivalent Length in Feet for Valves and Fittings 
Line Size 
OD (inches) 
Angle 
Valve 
Short 
Radius EL 
Long 
Radius EL 
3/8 
24 
2.8 
1/2 
24 
4.7 
3.2 
5/8 
25 
5.7 
3.9 
3/4 
25 
6.5 
4.5 
7/8 
28 
7.8 
5.3 
1-1/8 
29 
2.7 
1.9 
1-3/8 
33 
3.2 
2.2 
1-5/8 
34 
3.8 
2.6 
2-1/8 
39 
5.2 
3.4 
2-5/8 
44 
6.5 
4.2 
 
Figure 5: Liquid Line Sizing 
GPRC-20 
 
 
 
 
GPRC-30 
 
 
 
Total Equiv. 
Length (Ft) 
Liquid Line Size (OD") 
 
Total Equiv. 
Length (Ft) 
Liquid Line Size (OD") 
Horizontal 
or 
Downflow 
Upflow 
1-5 Ft 
Upflow 
6-10 Ft 
Upflow 
11-15 Ft 
 
Horizontal 
or 
Downflow 
Upflow 
1-5 Ft 
Upflow 
6-10 Ft 
Upflow 
11-15 Ft 
25 
1/2 
1/2 
1/2 
1/2 
 
25 
5/8 
5/8 
5/8 
5/8 
50 
1/2 
1/2 
1/2 
1/2 
 
50 
5/8 
5/8 
5/8 
5/8 
75 
1/2 
1/2 
1/2 
1/2 
 
75 
5/8 
5/8 
5/8 
5/8 
100 
1/2 
1/2 
1/2 
5/8 
 
100 
5/8 
5/8 
5/8 
5/8 
125 
1/2 
1/2 
1/2 
5/8 
 
125 
5/8 
5/8 
5/8 
5/8 
150 
1/2 
1/2 
5/8 
5/8 
 
150 
5/8 
5/8 
5/8 
5/8 
175 
1/2 
5/8 
5/8 
5/8 
 
175 
5/8 
5/8 
5/8 
3/4 
200 
1/2 
5/8 
5/8 
5/8 
 
200 
5/8 
5/8 
5/8 
3/4 
225 
1/2 
5/8 
5/8 
5/8 
 
225 
5/8 
5/8 
5/8 
3/4 
250 
5/8 
5/8 
5/8 
5/8 
 
250 
5/8 
5/8 
3/4 
3/4 
275 
5/8 
5/8 
5/8 
5/8 
 
275 
5/8 
5/8 
3/4 
3/4 
300 
5/8 
5/8 
5/8 
5/8 
 
300 
5/8 
5/8 
3/4 
3/4