Chapter 3: Installation 
19 of 90 
 
Figure 3: Typical GP20-50 Water Cooled Condenser Connections 
Air-Cooled Chiller Condensers 
Air-cooled chillers use the surrounding air to cool the condenser. Install the chiller in an area 
where there is free passage of air for condensing and provisions for removal of heated air 
from the area. Do not locate air-cooled chillers in locations where steam, hot air, or fume 
exhausts can be drawn into the chiller.  
Caution!  Clean air-cooled condensers and filters frequently. Failure to do so results in 
reduced capacity, increased operating costs, and possible failure of the 
equipment. Cleaning instructions can be found in the Maintenance chapter of 
this manual 
Normal maximum refrigerant condensing pressure with 95ºF (35ºC) air entering the 
condenser is 420 psi (2896 kPa). 
Condensing Air Temperature. Our air-cooled portable chillers are designed to operate at a 
minimum condenser entering air temperature of approximately 75ºF (24ºC). Operation of the 
equipment at a lower condenser entering air temperature can cause the chiller to malfunction. 
For entering air temperatures below 75ºF (24°C), an optional fan motor speed control is 
available. We recommend maintaining a minimum 75ºF (24°C) ambient temperature. 
Note: 
For all chillers manufactured with Variable Frequency Drives the 
voltage may vary up to 10% from the converter nominal voltage.  
However, the phase-to-phase input voltage imbalance must not 
exceed 3%.  If the input voltage does have an imbalance from phase 
to phase greater than 3% then a line reactor must be installed to 
prevent faults within the VFD. 
 
For remote condenser units, the maximum recommended motor 
cable length between the VFD and the motor without output chokes 
is 30 m (100 ft).  With output chokes the motor cable length may be 
extended to 65 m (195 ft).