3-10  Automatic Water Make-Up Option 
The chiller may be connected to an automatic make-up system if the optional package (pipe 
fittings, solenoid valve and 1/2” NPT city water make-up connection) is factory installed. 
Note: 
When the unit is selected with the optional, closed stainless steel tank, a 
pressure reducing valve is added to the automatic water make-up option.  This 
valve is set to be full open at 5 psig (0.3 bar). 
If the automatic make-up system is connected to a city water system, make provisions to 
prevent backflow contamination. Install an approved backflow preventer in accordance with 
local codes. 
Caution!  Adding straight city water into a glycol/water mixture dilutes the solution and 
eventually leads to system freeze-up. Damage from freeze-up is not covered by 
the warranty. 
To prevent system freeze-up in automatic make-up applications, we recommend using either 
a chemical feeder or make-up reservoir to replenish glycol. Contact the sales department for 
more information about these configurations. 
3-11  Initial Start-Up 

  Check the shipping papers against the serial tag to be sure chiller size, type and voltage 
is correct for the process that will be controlled.  Portable chillers are built with a 
voltage specific compressor and cannot be re-wired for an alternate voltage. 
 

  Check the transformer primary voltage connections to be sure they are configured for 
the electrical power you are using. The voltage at the main power connection must read 
within plus or minus ten percent (±10%) of the voltage listed on the serial tag. 
Electrical connections must conform to all applicable codes.