Chapter 3: Installation 
32 of 90 
 

  Complete chilled water To Process and From Process connections.  It is suggested that 
shut-off valves are added to unit to control the flow rate to process and for completely 
isolating the chiller from the process. 
 

  If the optional automatic water make-
up system was not installed on the 
chiller, remove the side panel to the 
left of the process connections and fill 
the tank and chilled water circuit 
piping until the tank is approximately 
¾ full.  Fill with water (or a 
water/glycol mixture if the desired 
setpoint is lower than 45°F (7°C)). 
The water/ glycol mixture should 
provide for freeze protection to at 
least 20°F (11ºC) below the leaving 
water temperature you want. 
 
 
 
 
 
To Process 
From Process