Chapter 4: Operation 
35 of 90 
Chapter 4:   Operation 
4-1  Panel Buttons, Indicator Lights, and Switches 
Microprocessor Controller 
The standard chillers use a microprocessor-based PID controller. The Carel PCO controller is 
located in the control enclosure.  The Carel PGD1 Interface is housed in a block of rigid 
plastic with a magnetic backing that allows the user to “stick” the interface on any metallic 
surface.  The GP20 through GP50 units come standard with a 10 ft (3 m) cable, and the GP70 
through GP210 units come standard with a 20 ft (6 m) cable.  Longer cables are available 
through the After Market Sales Group.  The controller is factory set and adjusted; no field 
adjustment to the internal controls is necessary. The standard operation range is 20ºF to 80ºF 
(-7ºC to 27ºC). 
Warning!  Operating the chiller setpoint below 45°F (7°C) without the proper 
amount of glycol for freeze protection could result in a damaged 
evaporator.  ACS Group does not warrant the freeze up of the 
evaporator under any circumstances. 
 
Figure 12: Controller Display