GP Series Portable Chillers 
Chapter 4: Operation 
37 of 90 
 
 
Enter the established Operator Password by depressing the 
 to move the 
position of the cursor, and then depressing the 
  or 
 button to 
increment or decrement the number.  Once all of the numbers have been 
entered depress the 
 to accept the password. The following screen will 
appear. 
 
Figure 15: Operator Setpoints Screen 
5.  Depress 
 to move the cursor to the CHILLED FLUID SP line.  Use the 
 or 
 button to increment or decrement the value.  Depress 
 to 
accept the value and move the cursor down one line. 
6.  Depress the 
 button twice to return to the main status screen. 
7.  Depress the 
 to start the chiller. 
8.  Check pump rotation 
9.  Check the pump amp draw and pump pressure. Make sure that the amp draw 
reading is within the running load and service factor amps. 
10. Operate the chiller, looking for any leaks and listening for unusual noises or 
vibrations that could indicate improper operation. 
Elevated sound level and substantially reduced current draw indicate reverse 
rotation. After several minutes of operation, the compressor internal protector 
trips. 
4-3  Status Screens 
The controller has eight (8) preconfigured status screens.  The main status screen (shown in 
Figure Figure 16) shows the main operating points of the chiller: Entering and Leaving fluid 
temperatures; Leaving fluid setpoint, pump discharge pressure, tank fluid level (depth), and 
percentage of hot-gas bypass output.