GP Series Portable Chillers 
Chapter 6: Troubleshooting 
55 of 90 
Auxilliary Alarm 
41  SC/W  This alarm is configurable 
 
Low Suction Pressure at Startup 
42 
CC 
Parameter set too short for 
remote condenser installation 
Adjust parameter for length of 
time to build suction pressure 
Refrigerant amount too low 
Contact Customer Service 
For Units with a Tempered Loop 
To ProcTemperature Sensor 
Failure 
43 
PC 
Loose or broken sensor wire 
Verify wiring of temperature 
sensor at sensor and terminal 
block of controller 
Process High Temp Fault 
44 
Process heater on 
Verify heater contactor 
operation 
Process cooling valve off 
Verify cooling valve operation 
Process High Temp Warning 
46 
Process heater on 
Verify heater contactor 
operation 
Process cooling valve off 
Verify cooling valve operation 
Process Low Temp Fault 
48 
Process heater off 
Verify heater contactor 
operation 
Process cooling valve on 
Verify cooling valve operation 
Process Low Temp Warning 
50 
Process heater off 
Verify heater contactor 
operation 
Process cooling valve on 
Verify cooling valve operation 
Pump 2 No Flow 
52  SC/W 
Optional process flow switch 
failure 
Verify operation of flow switch. 
Process valves closed 
Verify operation of process 
valves and adjust as necessary 
 
CC = Compressor Critical 
SC = System Critical 
PC = Process Critical  W = Warning 
Alarm Name 
Type  Possible Cause 
Solution 
Pump 2 Overload 
53  SC/W 
Motor circuit protector open 
Verify motor circuit protector 
operation. Verify motor wiring 
and amp draw while under load.   
Pump flow rate in excess of 
capacity 
Verify system valves are 
operational and properly set.  
Contact customer service or 
sales if pump is sized too small 
for application. 
High Temp Safety Switch 
54 
PC 
Heater failure 
Verify operation of heater and 
cooling valve.  .   
Cooling Valve failure 
Verify wiring at cooling valve 
and at terminal bloc 
Sensor failure 
Replace sensor if necessary. 
Phase Monitor Fault 
55 
SC 
Unit wired incorrectly 
Reverse two wires at line-side 
of power switch on electrical 
panel.   
Loss of phase during 
operation 
Verify sensor wiring at sensor 
and at terminal bloc.   
Sensor failure 
Replace sensor if necessary. 
From Proc Sensor Failure 
56 
Sensor wires loose from 
controller terminal block 
Verify wiring at sensor and at 
terminal block.  y. 
Sensor wires broke between 
sensor and controller terminal 
block. 
Replace sensor if necessar 
 
Non-Controller Related Issues 
Problem 
Possible cause 
Solution 
Unit does not run. 
No power. 
Check main disconnect, fuses, wiring, 
and power lead to unit. 
Wrong voltage supplied to unit. 
Voltage must be within plus or minus 
10% of nameplate rating.