GP Series Portable Chillers 
Chapter 6: Troubleshooting 
57 of 90 
 
Problem 
Possible cause 
Solution 
Pump runs; compressor does not. 
Leaving fluid setpoint
 
set higher 
than temperature of liquid in 
system. 
Lower the leaving fluid temperature 
below the leaving temperature you 
desire. 
Compressor internal overload or 
MCP is open. 
Allow time to cool and reset, then check 
for high/low volt-age. It must be within 
plus or minus 10% of the nameplate 
rating. 
Check for loose compressor electrical 
connections. 
Failed compressor motor 
Compressor contactor holding coil 
open. 
Repair or replace. 
Defective compressor auxiliary 
contact. 
Repair or replace. 
Broken wire in the compressor 
control circuit. 
Locate and repair. 
Pump runs, compressor cycles at 
short intervals. 
Plugged Y-strainer 
Clean 
Hot gas not coming on 
Check hot gas analog output value 
through status screen.  Contact Service 
if output value remains at 0% 
throughout compressor cycle. 
Low process water flow 
Check internal bypass valve to verify it 
is open and free of debris. 
 
Install bypass between to-and-from 
process line 
Unit runs continuously, but not 
enough cooling power
.
 
Restricted condenser air flow. 
Clean filters. 
Clean condenser. 
Unit low on refrigerant. 
Check the refrigerant charge by viewing 
sight glass on liquid line upstream of the 
expansion valve. 
Compressor not operating 
efficiently. 
Call service. 
Unit under-sized for application. 
Call sales rep.