Chapter 2: Functional Description 
8 of 90 
Process Fluid Temperature – The standard range for the leaving fluid temperature for this 
series of packaged chillers is 20°F to 80°F (-6.7°C to 26.7°C).  When the process requires 
fluid temperatures below 45°F (27.2°C) it is imperative that the process fluid is a mix of an 
industrial grade ethylene or propylene glycol and water to the proper percentage (by volume) 
to protect the system.  See Chapter 3 for a further discussion regarding the use of glycol 
within the system for these applications. 
WARNING! - ACS Group does not warrant the freeze up of the evaporator 
under any circumstances. 
Chilled Water Circuit 
Cooling water “To Process” and “From Process” 
connections are made at the female NPT couplings 
provided outside the unit.  
 
Warm coolant (water and glycol mixture) returns 
from the process and goes into the reservoir tank.  
 
The coolant is then pumped through the evaporator 
where it is cooled. 
 
The coolant flows to the process and returns to 
repeat the cycle. 
A process water bypass valve located between the supply 
line and reservoir tank (single pump models only) allows 
minimal flow through the unit during the intermittent 
fluctuating flow conditions. It is not intended to provide 
continuous full bypass flow.  
This minimal flow allows the flow switch to make when 
the process flow is stopped.  If the flow switch is not made the controller shuts down the 
compressor to prevent freezing up the evaporator.