Configuration Mode - MyMenu
Code
Name/Description
Adjustment range
Factory setting
LFr
T
M External reference value
-400 Hz to 400 Hz
-
This parameter allows to modify the frequency reference with the jog dial.
External keypad or local force mode configured.
External keypad or local force mode configured.
page
set to
LCC
and
and
page
different to
nO
. Visibility depends on the drive settings.
AIU1
T
M Analog input virtual
0% to 100%
-
This parameter allows to modify the frequency reference when
•
•
page
is set to
AIU1
• and
nO
.
Visible if reference channel active is integrated display (
set to
AIU1
).
bFr
M Standard motor frequency
50 Hz
50
60
60
External keypad or local force mode configured (FLOC = LCC) (not visible in the factory setting).
v
50 Hz
v
60 Hz
Set to 50 Hz or 60 Hz, taken from the motor rating plate. Changing
Set to 50 Hz or 60 Hz, taken from the motor rating plate. Changing
bFr
sets back parameters:
FrS
,
Ftd
and
HSP
: 50 Hz or 60 Hz
itH
is set to
nCr
nCr
according to drive rating
nPr
Watt or HP
nSP
according to drive rating
tFr
60 Hz or 72 Hz
Fr1
M Reference channel 1
AI1
AI1
LCC
Mdb
LCC
Mdb
AIUI
This parameter allows selection of the reference source.
v
Terminal
v
Remote display
v
Modbus
v
Integrated display with Jog dial
ACC
T
M Acceleration
0.0 s to 999.9 s
3.0 s
Acceleration time between 0 Hz and the
page
Make sure that this value is compatible with the inertia being driven.
dEC
T
M Deceleration
0.0 s to 999.9 s
3.0 s
Time to decelerate from the
page
to 0 Hz.
Make sure that this value is compatible with the inertia being driven.
LSP
T
M Low speed
0 Hz to HSP
0 Hz
Motor frequency at minimum reference
If
If
HSP
,
HSP2
,
HSP3
and
HSP4
are already set then
LSP
is limited to the minimum of those
values.
HSP
T
M High speed
LSP to tFr (Hz)
50 or 60 Hz
according to BFr,
max TFr
according to BFr,
max TFr
Motor frequency at maximum reference.
Check that this setting is appropriate for the motor and the application. The values of
Check that this setting is appropriate for the motor and the application. The values of
HSP
,
HSP2
,
HSP3
and
HSP4
are idependent but each
HSP
page
according to the following rules:
•
HSP
x is limited to
and
y
HSP
x y
• If
is decreased below the current HSPx value, then HSPx automatically decreases to the new
• Once
HSP
,
HSP2
,
HSP3
and
HSP4
is limited to their minimum.
T
Parameter that can be modified during operation or when stopped.