Schneider Electric 3.0A Manual Do Utilizador
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
48049-136-05
Appendix A—Register List
Rev. 01, 07/2012
© 1999–2012 Schneider Electric All Rights Reserved
36-EN
ENGLISH
Appendix A—Register List
List of Registers
The quantities are listed in alphabetical order
according to the SMS topic name.
according to the SMS topic name.
NOTE: A system scan rate of 500 ms or greater
is recommended to minimize communications
timeout issues.
is recommended to minimize communications
timeout issues.
This is an abbreviated list of registers. For a
complete list of registers, contact your local
sales office.
complete list of registers, contact your local
sales office.
To access available registers, the following address scheme applies.
Module
Module Name
Equation
Address Range
BCM
Circuit Breaker Communication Module --
1–47
CCM
Cradle Communication Module
BCM + 50
51–97
PM
Protection Module (Internal to trip unit)
BCM + 100
101–147
MM
Meter Module (Internal to trip unit)
BCM + 200
201–247
Table 10:
Register List
SMS Topic Name User Description
Number of
Registers
Registers
*
Register*
Module*
†
Units
Scale/Bitmask
810DBrkrStatus
Circuit Breaker Status
1
661
BCM
Bit 0; ON = closed, OFF = open
810DBrkrTripStat
Circuit Breaker Trip Unit Status
1
661
BCM
Bit 2; ON = tripped, OFF = not tripped
BCM_SN
BCM Serial Number
4
516
BCM
ASCII text
BkrPos
Circuit Breaker Position
1
661
CCM
Bit 8 = disconnected
Bit 9 = connected
Bit 10 = test position
Bit 9 = connected
Bit 10 = test position
DT_3Regs
Device Clock Date/Time
3
679
BCM
3-register date/time format
‡
EnableCloseBkr
Remote Closing Enabled
1
669
BCM
Bit 2; ON = enabled, OFF = not enabled
EnableOpenBkr
Remote Opening Enabled
1
669
BCM
Bit 1; ON = enabled, OFF = not enabled
EnableRemCtrl
Remote Control Enabled
1
669
BCM
Bit 3; ON = auto (enabled),
OFF = manual (not enabled)
OFF = manual (not enabled)
IA
Current A
1
8821
PM
A
Unity
IA_PCT
Current A % Load
1
8837
PM
%
Unity
IB
Current B
1
8822
PM
A
Unity
IB_PCT
Current B % Load
1
8838
PM
%
Unity
IC
Current C
1
8823
PM
A
Unity
IC_PCT
Current C % Load
1
8839
PM
%
Unity
IG
Current G
1
8825
PM
A
Unity
IG_PCT
Current G % Load
1
8841
PM
%
Unity
IG_PCT_VIGI
Current G (VIGI) % Load
1
8842
PM
%
Hundredths
IG_VIGI
Current G (VIGI)
1
8826
PM
A
Thousandths
IMax
Current Max Present
1
8820
PM
A
Unity
IN
Current N
1
8824
PM
A
Unity
IN_PCT
Current N % Load
1
8840
PM
%
Unity
LDPUValue
Long Delay Pickup Value
2
8756
PM
A
Modulo 10,000 format
**
MaxIA
Max Current A
1
8827
PM
A
Unity
MaxIB
Max Current B
1
8828
PM
A
Unity
MaxIC
Max Current C
1
8829
PM
A
Unity
MaxIG
Max Current G
1
8831
PM
A
Unity
MaxIG_VIGI
Max Current G (VIGI)
1
8832
PM
A
Thousandths
MaxIN
Max Current N
1
8830
PM
A
Unity
NominalCurrent
Circuit Breaker Nominal Current
1
8750
PM
A
Unity
ReadyToClose
Circuit Breaker Ready to Close
1
661
BCM
Bit 5; ON = yes, OFF = no
Continued on next page