VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS
11
69-1225—4
Table 8B. Pressure Regulator Specification Pressures (kPa).
a
 Low Fire setting range for VR8304Q 1/2 in. by 1/2 in. and 1/2 in. by 3.4 in. is 0.37  to 0.75 kPa.
Non-Regulating On-Off (U) Models
Non-regulating VR8204U Valves are designed for 
application in various parts of Europe where a separate, 
distinct, pressure regulator is required. The VR8204U is 
similar to the VR8204A in all other aspects and should be 
installed accordingly. 
MAINTENANCE
WARNING
Fire or Explosion Hazard.
Can cause property damage, severe injury, 
or death.
Do not disassemble the gas control; it contains 
no replaceable components. Attempted 
disassembly, repair, or cleaning can damage the 
control, resulting in gas leakage.
Regular preventive maintenance is important for 
applications in the commercial cooking and agricultural 
and industrial industries that place a heavy load on 
system controls because:
In many such applications, particularly commercial 
cooking, the equipment operates 100,000 to 200,000 
cycles per year. Such heavy cycling can wear out the 
gas control in one to two years.
Exposure to water, dirt, chemicals and heat can 
damage the gas control and shut down the control 
system.
The maintenance program should include regular 
checkout of the control as outlined in the Startup and 
Checkout section, and the control system as described in 
the appliance manufacturer literature.
Maintenance frequency must be determined individually 
for each application. Some considerations are:
Cycling frequency. Appliances that may cycle 20,000 
times annually should be checked monthly.
Intermittent use. Appliances that are used seasonally 
should be checked before shutdown and again before 
the next use.
Consequence of unexpected shutdown. Where the 
cost of an unexpected shutdown would be high, the 
system should be checked more often.
Dusty, wet, or corrosive environments. Since these 
environments can cause the gas control to deteriorate 
more rapidly, the system should be checked more 
often.
The system should be replaced if:
It does not perform properly on checkout or 
troubleshooting.
The gas control is likely to have operated for more 
than 200,000 cycles.
The control is wet or looks as if it has been wet.
SERVICE
WARNING
Fire or Explosion Hazard.
Can cause property damage,  severe injury 
or death.
Do not disassemble the control; it contains no 
replaceable components. Attempted 
disassembly, repair, or cleaning can damage 
the gas control, resulting in gas leakage.
CAUTION
Equipment Damage.
Can burn out valve coil terminals.
Never apply a jumper across (or short) the valve 
coil terminals, even temporarily.
After servicing, verify proper system operation.
If Main Burner Does Not Come 
On With Call For Heat
1.
Confirm the gas control knob is in the ON position.
2.
Adjust thermostat several degrees above room 
temperature.
3.
Using ac voltmeter, check for 24V at gas control:
• If pilot lights, measure across MV/PV and MV.
• If pilot does not light, measure across MV/PV 
and PV before safety lockout occurs.
4.
If voltage is incorrect or not present, check control 
circuit for proper operation.
5.
If 24V is present, replace gas control.
Model Type
Type of 
Gas
Nominal Inlet 
Pressure Range
Factory Set Nominal Outlet 
Pressure
Setting Range
Step
Full Rate
Step
Full Rate
Standard, 
Slow
NAT
1.2 to 1.7
0.9
0.7 to 1.2
LP
2.9 to 3.9
2.5
2.0 to 3.0
Step
NAT
1.2 to 1.7
0.2
0.9
None
0.17 to 0.48
LP
2.9 to 3.9
0.5
2.5
None
1.4 to 1.37
Two-stage
NAT
1.2 to 1.7
0.48 Low
0.9 High
0.22 to 0.75 Low
a
0.75 to 1.2 High
LP
2.9 to 3.9
1.2 Low
2.5 High
0.9 to 1.4 Low
2.0 to 2.5 High