GENERAL VENTING
These models are approved for use with DESA 58 
Series, rigid type direct vent pipe as supplied by 
DESA or with approved types of flexible vent pipe 
(not supplied) when appropriately sized for an 8" 
outer and 5" inner diameter application.
Your fireplace is approved to be vented either hori-
zontally through a side wall, or vertically through 
a roofline using the following guidelines:
•  Only use DESA supplied or approved types 
of venting components or kits. Do not mix 
different types of vent components, modify 
vent  components  or  custom  fabricate  vent 
components for use in any one installation.
•  Minimum clearance between vent pipes and 
combustible materials is 1", except where stated 
otherwise.
•  Combustible material may be flush with the top 
front of fireplace with a maximum thickness 
of 3/4".
•  Do not recess venting terminals into a wall 
or siding.
•  Do not install vent terminals below grade level. 
Maintain a minimum height of 12" above snow 
line.
•  Do not terminate venting system into an attic 
or garage.
•  If using a venting configuration of only hori-
zontal venting with no vertical run, a 1/4" rise 
for every 12" of run toward the termination is 
required.
•  There must not be any obstruction such as 
bushes, garden sheds, fences, decks, or util-
ity buildings within 24" from the front of the 
termination cap.
•  Do not locate termination cap where excessive 
snow or ice build up may occur. Be sure to clear 
vent termination area after snow falls to prevent 
accidental blockage of venting system. When 
using snow blowers, do not direct snow towards 
vent termination area.
VENT TERMINATION CLEARANCES
The final position of your appliance depends on 
the location of the vent termination in relation to 
the clearances that must be observed as shown in 
Figure 11, page 9.
You may avoid extra framing by positioning your 
fireplace against an already existing framing mem-
ber. The back of the fireplace may be positioned 
directly against a combustible wall.
*Check with local codes or with the CANCGA 
B149.1 or B149.2 Installation Codes for Canada 
installations. In the USA, follow the current Na-
tional Fuel Gas Fuel Gas Code, ANS Z223.1 also 
known as NFPA 54.