Jacuzzi J-210 Manual Do Utilizador

Página de 60
J-200 Series
7.0 
electrical wiring Instructions
ImporTanT noTICe: The electrical wiring of this spa 
must meet the requirements of the National Electrical 
Code/USA (NEC) and any applicable state or local codes. 
The electrical circuit must be installed by a qualified electrician and 
approved by a local building/electrical inspection authority.
1.  Convertible 120/240V Power Models:
!
• 
 
DanGer:
 to DeCrease the risk oF shoCk, 
proDuCT DamaGe or eleCTrICal FIre. 
 
120v “plug-in” operation: This spa must operate on the supplied 
120V GFCI cord at its original length or must be hard-wired for longer 
runs. NEVER USE AN EXTENSION CORD FOR ANY REASON! 
Convertible 120/240v heater operation:
• 
 The included 120V 
GFCI cord must be discarded for 240V heater operation. This spa 
must be hard wired. Supplying power to either configuration above 
which is not in accordance with these instructions will void both the 
independent testing agency listing and the manufacturer’s warranty.
2.  Dedicated 230V-240V models must be permanently connected 
(hard-wired) to the power supply. No plug-in connections or 
extension cords are to be used in conjunction with the operation 
of this spa. Supplying power to the spa which is not in accordance 
with these instructions will void both the independent testing agency 
listing and the manufacturer’s warranty.
3.  The power supplied to this spa must be a dedicated circuit with no 
other appliances or lights sharing the power provided by the circuit.
4.  To determine the current, voltage and wire size required, refer to 
section 6.0 “Power Requirements” (page 13).
Wire size must be appropriate per NEC/USA and/or local codes.
• 
We recommend type THHN wire.
• 
All wiring must be copper to ensure proper connections. 
• 
Do not use 
aluminum wire.
When using wire larger than #6 (10 mm²), add a junction box near 
• 
the spa and reduce to short lengths of #8 (8.4 mm²) wire to connect 
to the spa.
5.  The electrical supply for this product must include a suitably rated 
switch or circuit breaker to open all ungrounded supply conductors 
to comply with Section 422-20 of the National Electrical Code/USA, 
ANSI/NFPA 70. The disconnecting means must be readily accessible 
to the spa’s occupant but installed at least 5 feet (1.5m) from spa 
water. 
6.  The electrical circuit supplied for the spa must include a suitable 
ground fault circuit interrupter (GFCI) as required by NEC/USA Article 
680-42.
7.  To gain access to the spa’s power terminal block, remove the screws 
securing the synthetic cabinet panel under the control panel (Figure A). 
16