41
3) Drain Timer
The Drain Timer is factory-adjusted, and no adjustment is required.
SETTING
TIME
Dip Switch
Dip Switch
No. 3
No. 4
T1
T2
OFF
OFF
10 seconds
150 seconds
ON
OFF
10 seconds
180 seconds
OFF
ON
10 seconds
120 seconds
ON
ON
20 seconds
180 seconds
T1: Time to drain the Water Tank
T2: Time to restrain defrost completion
4) Drain Counter
CAUTION
Do not adjust the Drain Counter, or the Evaporator may freeze up.
The Drain Counter is factory-adjusted to drain the Water Tank every 10 cycles, and no
adjustment is required. However, where water quality is bad and the icemaker needs a
pump drain more often, the Drain Counter can be adjusted as shown in the table below:
2) Defrost Timer
No adjustment is required under normal use, as the Defrost Timer is adjusted to the suit-
able position.  However, if necessary when all the ice formed on the Evaporator does not
fall into the bin in the harvest cycle, adjust the Defrost Timer to longer setting by adjusting
the Dip Switch (No. 1 & 2) on the Controller Board.
SETTING
TIME
Dip Switch
Dip Switch
No. 1
No. 2
OFF
OFF
  60 seconds
ON
OFF
  90 seconds
OFF
ON
120 seconds
ON
ON
180 seconds