Hoshizaki HUR40a Manual Do Utilizador

Página de 64
6
Code Item
Setting and Display Range
Default
Refrigerator
Freezer
Auxiliary Code
1
section
2
section
Q5 and
earlier
Q6 and
later
F0 Defrost Interval
1 to 1 hours in 1 hour increments
6
6
6
F1 Defrost Termination 
Temperature
Refrigerator: 59 to 68°F (15 to 0°C) in 
one degree increments
Freezer: 41 to 68°F (5 to 0°C) in one 
degree increments
59°F
59°F
41°F
F Setpoint 
Temperature 
Differential 
(upper and lower)
0 to 6.3°F in increments of .9°F  
(0 to 3.5°C in increments of .5°C) 
0°F, -45°F
(0°C, 
-.5°C )
(decimal
is not
displayed)
0°F, -36°F
(.0, -
.0°C)
(decimal
is not
displayed)
0°F, -63°F
(0°C, 
-3.5°C)
(decimal
is not
displayed)
0°F, -36°F
(.0, 
-.0°C)
(decimal
is not
displayed)
F3 High Temperature 
Alarm Delay Time
0 to 180 minutes in 60 minute 
increments 
(0=0; 1=60; =10; 3=180 minutes)
F4 Low Temperature 
Alarm Delay Time
0 or 60 minutes 
(0=0; 1=60 minutes)
1
1
1
F5 Temperature Dis-
play
Fahrenheit or Celsius
°F
°F
°F
F6 Alarm History
Displays alarm history - maximum 8 
alarms
NA
NA
NA
F7 Compressor Run 
Time
Displays run time between two most 
recent defrosts
NA
NA
NA
F8 Not Used
NA
NA
NA
F9 Not Used
NA
NA
NA
3. Settings and Diagnostics Menu
To gain access to the settings, see "II.D.1. Gaining Access to Settings and Diagnostics." 
Once inside this menu, press the MANUAL DEFROST button to scroll through the menu 
and the 
 unmarked, blank button at any point to view the current setting. Press the 
MANUAL DEFROST button to return to the menu screen.