Hoshizaki fh1-ssb Manual Suplementar

Página de 63
4
2. Diagnostics Menu 
Access to diagnostic menu is gained by pressing and holding the up/down arrows and 
the "ENTER" button together for three seconds. Scroll through menu options using the 
"ENTER" button. Change options using up/down arrows. Reset alarm conditions using 
the RESET button. To exit, press the "ENTER" button until normal display returns. To exit 
diagnostic menu at any point in the menu, press and hold the "ENTER" button for three 
seconds. Diagnostic menu will remain on display for 10 minutes after the last keystroke, 
then automatically revert to normal operation mode (cabinet temperature display). All 
information given in degrees will automatically convert to the appropriate programmed 
scale (°F or °C).
Display Definition
1OFF
Displays cabinet temperature.
1 ON
Displays evaporator temperature. Display will automatically revert to cabinet sensor after five minutes.
OFF 
(Freezer 
Only)
Manual defrost initiation option not activated.
 ON 
(Freezer 
Only)
Manual defrost initiation option activated. Control will begin defrost cycle once user returns to operating 
mode by cycling through menus. Manual defrost does not eliminate or change times on any scheduled 
defrost cycles.
3OFF
Unconditional alarm reset option not activated.
3 ON
Unconditional alarm reset option activated. Changing from 3OFF to 3 ON resets all alarm display codes 
simultaneously. This is a complete clearing of alarms.
4 16
Right two digits represent compressor run time in last 4 hours to the nearest hour. Example: 16 hours total 
run time in the last 4 hours. Value is every 4 hours.
5 50
Right two digits represent compressor on time percentage for the last 5 run cycles. A run cycle begins when 
the compressor switches from off to on and ends the next time it switches from off to on. (See diagram 
below). Example: 50% run time over the last 5 run cycles. 
Value is calculated as follows: Percent on time = On time last 5 cycles/total time last 5 cycles. Value is 
saved every 5 cycles. 
Note: "On time last 5 cycles" does not include an on time that was terminated by a defrost cycle or the first 
on time after a defrost, and "Total time last 5 cycles" does not include an on or off time that was terminated 
by a defrost cycle, the time spent in defrost or the first on time after a defrost. 
6 45
Right two digits represent compressor run time for the last run cycle. Example: 45 minutes of compressor 
run time in last run cycle.
7 45
 
(Freezer 
Only)
Right two digits represent length of time for the last defrost cycle in minutes. Example: 45 minutes in last 
defrost cycle.
8 67
Right two digits represent highest temperature recorded during the last high temperature alarm. Example: 
Temperature reached 67 degrees during last high temperature alarm. Display will show "8--" if there has not 
been a high temperature alarm. Value is saved every 8.5 minutes when in alarm.
9-10
Right three places represent lowest temperature recorded during the last low temperature alarm. Example: 
Temperature reached -10 degrees during the last low temperature alarm. Display will show "9--" if there has 
not been a low temperature alarm. Value is saved every 8.5 minutes when in alarm.
The diagram below is an example of run cycle used to calculate run time: